Kirk Key Interlock Company
INDEX
INTERLOCKS
Brass Interlocks
Hybrid Series Interlocks316 Stainless Steel Interlocks
DOWNLOADS
Data Sheets
DrawingsAPPLICATION INFOCOMMON SCHEMESDUPLICATE KEYSKey Release FormCORPORATEORDERCONTACT

Email Kirk Key:
sales@kirkkey.com

 

 

 

Contents | Introduction | Symbols Legend | Scheme Book

Interlock Application - Switch and Breaker

Scheme # 1

To prevent opening of switch A when breaker B is closed.

Interlock Application Scheme # 1 - Switch and Breaker

Switch A and breaker B are in closed position. Key A-1 is held in breaker B interlock.

  1.
2.

3.

4.
Open breaker.
Turn key A-1 in L-O interlock on breaker B to lock open. Key A-1 is now free.
Insert key A-1 in L-C interlock on switch A and turn to unlock.
Open switch A. Key A-1 is now held.

Reverse sequence to restore service.

Links for more interlock application scheme information:

Contents | Introduction | Symbols Legend | Scheme Book

Scheme # 25
Scheme # 26
Scheme # 27
Scheme # 28
Scheme # 29
Scheme # 30
Scheme # 31
Scheme # 32

Scheme # 33 Scheme # 34
Scheme # 35
Scheme # 35A

Scheme # 36

Scheme # 37
Scheme # 38
Scheme # 39
Scheme # 40
Scheme # 41
Scheme # 42
Scheme # 42A
Scheme # 42B

Scheme # 43
Scheme # 43A
Scheme # 44
Scheme # 45
Scheme # 45A

 
   

Copyright © 2000-2007 Kirk Key Interlock. All Rights Reserved.
Terms and Conditions
Web Site, Graphics & Design by R.S.Venables