Scheme # 10
To
prevent operation of disconnects A and B and by-pass disconnect
C under load. Provides for closing of by-pass disconnect
C before breaker circuit is opened, or permits breaker
circuit to be opened with by-pass disconnect C remaining
open.

Disconnects
A and B and breaker D normally closed. By-pass disconnect
C normally open. Keys A-1, A-2, and A-4 normally held
in locks as indicated. Key A-3 normally free.
To transfer load from breaker and disconnects to by-pass
switch:
|
|
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
|
Obtain key A-3 which is free and insures that both
disconnects A and B are locked closed.
Insert key A-3 in L-C interlock on breaker D and turn
to lock closed. Key A-3 is held and key A-4 is
now free.
Insert key A-4 in L-O-C interlock on by-pass
disconnect C and turn to unlock. Key A-4 is now held.
Close by-pass disconnect C.
Turn key A-4 in L-O-C interlock on by-pass disconnect
C to lock closed. Key A-4 is now free.
Insert key A-4 in L-C interlock on breaker D and turn
to unlock. Key A-4 is held and key A-3 is now free.
Open breaker D.
Turn key A-1 in L-O interlock on breaker D to lock
open. Key A-1 is now free.
Insert keys A-1 and A-3 in L-C interlock on disconnect
A and turn to unlock. Keys A-1 and A-3 are now held.
Open disconnect A.
Turn key A-2 in L-O interlock on disconnect A to lock
open. Key A-2 is now free.
Insert key A-2 in L-C interlock on disconnect B and
turn to unlock. Key A-2 is now held.
Open disconnect B.
Turn key A-1 in L-O interlock on disconnect B to lock
open. Key A-1 is now free.
Insert key A-1 in L-O interlock on breaker D and turn
to unlock to permit operation during servicing. |
To open disconnects A and B and breaker D, leaving by-pass
disconnect C open:
|
|
1.
|
Proceed from normal position with operations as in
7 to 15 above. |
|