Application
- Isolating Switches and Breaker
or Regulator with By-Pass Switch
Scheme # 10A
To
prevent operation of disconnect A and B and by-pass disconnect
C under load. Permits by-pass disconnect C to operate
only when regulator is in neutral position. Permits isolating
regulator for servicing.

Disconnects
A and B are normally closed. Regulator is normally in
operation. By-pass disconnect C is normally open.
One key A-1 is held in regulator L-N (locked neutral)
interlock and the second key A-1 is held in L-O interlock
on disconnect A. Key A-2 is held in L-C interlock on disconnect
C. Key A-3 is held in L-O interlock on disconnect B.
|
|
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
.
|
Operate regulator to neutral position.
Turn key A-1 in L-N interlock on regulator to lock
in neutral position. Key A-1 is now free.
Insert key A-1 in L-O interlock on by-pass disconnect
C and turn to unlock. Key A-1 is now held.
Close by-pass disconnect C.
Turn key A-2 in L-C interlock on by-pass disconnect
C to lock closed. Key A-2 is now free.
Insert key A-2 in L-C interlock on disconnect B and
turn to unlock. Key A-2 is now held.
Open disconnect B.
Turn key A-3 in L-O interlock on disconnect B to lock
open. Key A-3 is now free.
Insert key A-3 in L-C interlock on disconnect A and
turn to unlock. Key A-3 is now held.
Open disconnect A.
Turn key A-1 in L-O interlock on disconnect A to lock
open. Key A-1 is now free.
Insert key A-1 in regulator L-N interlock and turn
to unlock. This permits regulator to be operated during
inspection and servicing. |
Reverse
sequence to restore service.
|