Scheme # 12
To
prevent paralleling of lines A and B. Single load, fed
from either source. To prevent operation of disconnect
switches A and B when breaker C is closed.

Breaker
C and disconnect A are shown in closed position. Disconnect
B is shown in open position. Key A-1 is held in breaker
C interlock. Key A-2 is held in L-O interlock on disconnect
A.
To service breaker:
|
|
1.
2.
3.
4.
5.
6. |
Open breaker C.
Turn key A-1 in L-O interlock on breaker to lock open.
Key A-1 is now free.
Insert key A-1 in L-O-C interlock on disconnect A
and turn to unlock. Key A-1 is now held.
Open disconnect A.
Turn key A-1 in L-O-C interlock on disconnect A to
lock open. Key A-1 is now free.
Return key A-1 to breaker interlock and unlock for
operation of breaker during servicing. |
To
transfer load from line A to line B:
|
|
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
|
Open breaker C.
Turn key A-1 in L-O interlock on breaker to lock open.
Key A-1 is now free.
Insert key A-1 in L-O-C interlock on disconnect A
and turn to unlock. Key A-1 is now held.
Open disconnect A.
Turn key A-1 in L-O-C interlock and key A-2 in L-O
interlock on disconnect A to lock open. Keys A-1 and
A-2 are now free.
Insert key A-1 in L-O-C interlock on disconnect B
and turn to unlock. Key A-1 is now held.
Insert key A-2 in L-O interlock on disconnect B and
turn to unlock. Key A-2 is now held.
Close disconnect B.
Turn key A-1 in L-O-C interlock on disconnect B to
lock closed. Key A-1 is now free.
Insert key A-1 in breaker interlock and turn to unlock.
Key A-1 is now held.
Close breaker. |
Reverse
sequence to restore service through line A.
|