- Prevent Paralleling of Lines
Scheme # 13
To
prevent paralleling of lines A and B. Two loads, fed from
either source.

Breaker
A is closed to supply load M. Breaker B is closed to supply
load N. Tie-breaker C is open. Keys A-1 are held in interlocks
on both breakers A and B. Tie-breaker C cannot be closed
unless either A or B is locked open.
To transfer load N to breaker A:
|
|
1.
2.
3.
4.
|
Open breaker B.
Turn key A-1 in L-O interlock on breaker B to lock
open. Key A-1 is now free.
Insert key A-1 in L-O interlock on tie-breaker C and
turn to unlock. Key A-1 is now held.
Close tie-breaker C. |
Reverse
sequence to restore service.
Load M can be supplied through breaker B in a similar
manner.
|