Contents
| Introduction
| Symbols
Legend | Scheme
Book
Interlock
Application
- Switch and Breaker
Scheme # 2
To
prevent operation of switch A when breaker B is closed.
Permits re-closing of breaker for servicing when switch
is locked open.

Switch A and breaker B are in closed position. Key A-1
is held in breaker B interlock.
|
|
1.
2.
3.
4.
5.
6. |
Open breaker.
Turn key A-1 in L-O interlock on breaker B to lock
open. Key A-1 is now free.
Insert key A-1 in L-O-C interlock on switch A and
turn to unlock.
Open switch A. Key A-1 is now held.
Turn key A-1 in L-O-C interlock on switch A to lock
open. Key A-1 is now free.
Return Key A-1 to breaker interlock and unlock for
operation during servicing period. |
Reverse
sequence to restore service. |