Application
- Prevent Paralleling of Lines
Scheme # 20
To
prevent paralleling three power sources through a common
tie bus not normally in service. To permit feeding any
load bus from a second power source through the tie bus.
To permit one power source to supply all three load busses
through the tie bus.

Breakers
A, B, and C are normally closed. Breakers D, E, and F
are normally open. Under normal conditions keys A-1 and
A-5 are held in breaker A interlock, keys A-2 and A-5
are held in breaker B interlock, and keys A-3 and A-5
are held in breaker C interlock.
To transfer load from line No. 1 to line No. 2 or line
No. 3 through the tie bus, proceed as follows:
|
|
1.
2.
3.
4.
5.
6.
|
Open breaker A.
Turn key A-1 in L-O interlock on breaker A to lock
breaker open. Keys A-1 and A-5 are now free.
Insert key A-1 in L-O interlock on breaker D and turn
to unlock. Key A-1 is now held.
Close breaker D.
Insert key A-5 in L-O interlock on either breaker
E or F and turn to unlock. Key A-5 is now held.
Closer breaker E or F (whichever is selected). |
Reverse
sequence to restore load to line No. 1.
To transfer load from lines No. 1 and No. 2 to line No.
3 through tie bus, proceed as follows:
|
|
1.
2.
3.
4.
5.
6.
7.
|
Close breaker D as per steps 1 to 4 above.
Open breaker B.
Turn key A-2 in L-O interlock on breaker B to lock
breaker open. Keys A-2 and A-5 are now free.
Insert key A-2 in L-O interlock on breaker E and turn
to unlock. Key A-2 is now held.
Close breaker E.
Insert one of the A-5 keys from either breaker A or
B in L-O interlock on breaker F and turn to unlock.
Key A-5 is now held.
Close breaker F. |
Reverse
sequence to restore load to lines No. 1 and No. 2.

|