Contents
| Introduction
| Symbols
Legend | Scheme
Book
Interlock
Application
- Prevent Paralleling of Lines
Scheme # 21
To
prevent paralleling three power sources through a common
tie bus not normally in service. To permit feeding any
load bus from a second power source through the tie bus
only when authorized by supervisor. To permit one power
source to supply all three load busses through the tie
bus only when authorized by supervisor.

Breakers
A, B, and C are normally closed. Breakers D, E, and F
are normally open. Under normal conditions key A-1 is
held in breaker A interlock, key A-2 is held in breaker
B interlock, and key A-3 is held in breaker C interlock.
Key A-5 is retained by supervisor.
To transfer load from line No. 1 to line No. 2 or line
No. 3 through tie bus, proceed as follows:
|
|
1.
2.
3.
4.
5.
6.
|
Open breaker A.
Turn key A-1 in L-O interlock on breaker A to lock
breaker open. Key A-1 is now free.
Insert key A-1 in L-O interlock on breaker D and turn
to unlock. Key A-1 is now held.
Close breaker D.
Insert supervisor's key A-5 (only one A-5 is available)
in L-O interlock on either breaker E or F and turn
to unlock. Key A-5 is now held.
Close breaker E or F (whichever is selected). |
Reverse
sequence to restore load to line No. 1.
To transfer load from lines No. 1 and No. 2 to line No.
3 through tie bus, proceed as follows:
|
|
1.
2.
3.
4.
5.
6.
7.
|
Close breaker D as per steps 1 to 4 above.
Open breaker B.
Turn key A-2 in L-O interlock on breaker B to lock
breaker open. Key A-2 is now free.
Insert key A-2 in L-O interlock on breaker E and turn
to unlock. Key A-2 is now held.
Close breaker E.
Insert supervisor's key A-5 in L-O interlock on breaker
F and turn to unlock. Key A-5 is now held.
Close breaker F. |
Reverse
sequence to restore load to lines No. 1 and No. 2.

|