- Prevent Paralleling of Lines
Scheme # 22
To
prevent paralleling incoming primary sources, lines 1
and 2, through primary tie bus disconnect. To prevent
operation (open or closed) of the disconnects under load.
Permits one power source to supply both loads through
tie bus.

Under
normal conditions breakers A and B are closed, disconnects
C and D are lock closed, and tie bus disconnect T is locked
open. Keys A-1 are held in L-O interlock on breaker A
and L-C interlock on tie bus disconnect T. Keys A-2 are
held in L-O interlock on disconnects C and D. Keys A-3
are held in L-O interlock on breaker B and L-C interlock
on tie bus disconnect T. Keys A-4 (free keys) are shown
in removable position in the L-C interlocks on disconnects
C and D.
To transfer load No. 1 from line 1 to line 2 through bus
tie disconnect T, proceed as follows:
|
|
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
|
Open breaker A.
Turn key A-1 in L-O interlock on breaker A to lock
open. Key A-1 is now free.
Insert key A-1 in L-C interlock on disconnect C and
turn to unlock. Keys A-1 and A-4 are now held.
Open disconnect C.
Turn key A-2 in L-O interlock on disconnect C to lock
open. Key A-2 is now free.
Insert keys A-2 and free key A-4 (from L-C interlock
on disconnect D) in L-O interlock on bus tie disconnect
T and turn to unlock. Keys A-2 and A-4 are now held.
Close tie bus disconnect T.
Turn key A-3 in L-C interlock on disconnect T to lock
closed. Keys A-1 and A-3 are now free.
Insert key A-1 in L-O interlock on breaker A and turn
to unlock. Key A-1 is now held.
Close breaker A. |
Reverse
sequence to restore load No. 1 to line 1. To transfer
load No. 2 from line 2 to line 1 through bus tie disconnect
T, proceed in a similar manner.
|