Interlock Application - Prevent Paralleling of Lines

Scheme # 23

To prevent paralleling incoming primary sources, lines 1 and 2, through the primary tie bus disconnect or the secondary tie bus breaker. To prevent operation (open or closed) of the disconnects under load. Permits one power source to supply both loads through either the primary or secondary tie bus.

Interlock Application Scheme #  23 - Preven Paralleling of Lines

Under normal conditions breakers A and B are closed, breaker C is locked open, disconnects D and E are locked closed, and tie disconnect T is locked open. Keys A-1 are held in L-O interlock on breaker A and L-C interlock on primary tie bus disconnect T. Keys A-2 are held in L-O interlocks on disconnects D and E. Keys A-3 are held in L-O interlock on breaker B and L-C interlock on primary tie bus disconnect T. Keys A-4 (free keys) are shown in removable position in the L-C interlocks on disconnects D and E. Keys A-5 are held in L-O interlocks on breakers A and B.

To transfer load No. 1 from line 1 to line 2 through primary bus tie disconnect T, proceed as follows:

  1.
2.

3.


4.
5.

6.



7.
8.

9.

10.
Open breaker A.
Turn key A-1 in L-O interlock on breaker A to lock open. Keys A-1 and A-5 are now free.
Insert key A-1 and free key A-4 in L-C interlock on disconnect D and turn to unlock. Keys A-1 and A-4 are now held.
Open disconnect D.
Turn key A-2 in L-O interlock on disconnect D to lock open. Key A-2 is now free.
Insert key A-2 and free key A-4 (from L-C interlock on disconnect E) in L-O interlock on primary bus tie disconnect T and turn to unlock. Keys A-2 and A-4 are now held.
Close bus tie disconnect T.
Turn key A-3 in L-C interlock on bus tie disconnect T to lock closed. Keys A-1 and A-3 are now removable.
Insert key A-1 in L-O interlock on breaker A and turn to unlock. Key A-1 is now held.
Close breaker A.

Reverse procedure to restore service to line 1. Load No. 2 can be supplied from No. 1 through the primary bus tie in a similar manner.

To transfer load No. 1 from line 1 to line 2 through the secondary tie breaker C, proceed as follows:

  1.
2.

3.

4.
Open breaker A.
Turn key A-1 in L-O interlock on breaker A to lock open. Keys A-1 and A-5 are now removable.
Insert key A-5 in L-O interlock on tie breaker C and turn to unlock. Key A-5 is now held.
Close tie breaker C.

Reverse procedure to restore service on line 1. Load No. 2 can be supplied from line No. 1 through the secondary tie breaker C in a similar manner.


Links for more interlock application scheme information:

Contents | Introduction | Symbols Legend | Scheme Book

Scheme # 25
Scheme # 26
Scheme # 27
Scheme # 28
Scheme # 29
Scheme # 30
Scheme # 31
Scheme # 32

Scheme # 33 Scheme # 34
Scheme # 35
Scheme # 35A

Scheme # 36

Scheme # 37
Scheme # 38
Scheme # 39
Scheme # 40
Scheme # 41
Scheme # 42
Scheme # 42A
Scheme # 42B

Scheme # 43
Scheme # 43A
Scheme # 44
Scheme # 45
Scheme # 45A

 
   

Copyright © 2000-2007 Kirk Key Interlock. All Rights Reserved.
Terms and Conditions
Web Site, Graphics & Design by R.S.Venables