Contents
| Introduction
| Symbols
Legend | Scheme
Book
Interlock
Application
- Interrupter Switch
Scheme # 28
To
prevent dropping load when shifting from one source to
the other. To prevent opening both interrupter switches
A and B at the same time. Permits both interrupter switches
to be closed at the same time.

Interrupter
switch A is shown closed and interrupter switch B is shown
open. Key A-1 is held in interrupter B interlock.
|
|
1.
2.
3.
4.
|
Close interrupter B.
Turn key A-1 in L-C interlock on interrupter B to
lock closed. Key A-1 is now free.
Insert key A-1 in L-C interlock on interrupter A and
turn to unlock. Key A-1 is now held.
Open interrupter A. |
Reverse
sequence to restore service through interrupter B.
|