Interlock Application - Interrupter Switch

Scheme # 28

To prevent dropping load when shifting from one source to the other. To prevent opening both interrupter switches A and B at the same time. Permits both interrupter switches to be closed at the same time.

Interlock Application Scheme # 28 - Interrupter Switch

Interrupter switch A is shown closed and interrupter switch B is shown open. Key A-1 is held in interrupter B interlock.

  1.
2.

3.

4.
Close interrupter B.
Turn key A-1 in L-C interlock on interrupter B to lock closed. Key A-1 is now free.
Insert key A-1 in L-C interlock on interrupter A and turn to unlock. Key A-1 is now held.
Open interrupter A.

Reverse sequence to restore service through interrupter B.


Links for more interlock application scheme information:

Contents | Introduction | Symbols Legend | Scheme Book

Scheme # 25
Scheme # 26
Scheme # 27
Scheme # 28
Scheme # 29
Scheme # 30
Scheme # 31
Scheme # 32

Scheme # 33 Scheme # 34
Scheme # 35
Scheme # 35A

Scheme # 36

Scheme # 37
Scheme # 38
Scheme # 39
Scheme # 40
Scheme # 41
Scheme # 42
Scheme # 42A
Scheme # 42B

Scheme # 43
Scheme # 43A
Scheme # 44
Scheme # 45
Scheme # 45A

 
   

Copyright © 2000-2007 Kirk Key Interlock. All Rights Reserved.
Terms and Conditions
Web Site, Graphics & Design by R.S.Venables