Scheme # 29
To
prevent paralleling lines A and B requires dropping load
when shifting from one source to the other. To prevent
closing both interrupter switches A and B at the same
time. Permits both interrupter switches to be opened at
the same time.

Interrupter
switch A is shown closed and interrupter switch B is shown
open. Key A-1 is held in interrupter switch A interlock.
|
|
1.
2.
3.
4.
|
Open interrupter A.
Turn key A-1 in L-O interlock on interrupter A to
lock open. Key A-1 is now free.
Insert key A-1 in L-O interlock on interrupter B and
turn to unlock. Key A-1 is now held.
Close interrupter B. |
Reverse
sequence to restore service through interrupter A.
|