Contents
| Introduction
| Symbols
Legend | Scheme
Book
Interlock
Application
- Interrupter Switch
Scheme # 31
To
prevent operation (closed, open, or closed) of interrupter
switch when breaker is closed. Permits the breaker to
be serviced and operated while the interrupter switch
is locked open.

Breaker
and interrupter are shown in closed position, connected
to line B. Key A-1 is held in breaker interlock.
To service breaker, proceed as follows:
|
|
1.
2.
3.
4.
5.
6.
|
Open breaker.
Turn key A-1 in L-O interlock on breaker to lock open.
Key A-1 is now free.
Insert key A-1 in L-C-O-C interlock on interrupter
and turn to unlock. Key A-1 is now held.
Open interrupter.
Turn key A-1 in L-C-O-C interlock on interrupter to
lock open. Key A-1 is now free.
Return key A-1 to breaker interlock and unlock for
operation of breaker during servicing. |
Reverse
sequence to restore service through either line A
or line B.
To transfer interrupter from line B to line A:
|
|
1.
2.
3.
4.
5.
|
Proceed from normal position with operations as in
steps 1 through 3 above.
Open interrupter switch from line B and connect
to line A.
Turn key A-1 in L-C-O-C interlock on interrupter to
lock closed. Key A-1 is now free.
Insert key A-1 in L-O interlock on breaker and turn
to unlock. Key A-1 is now held.
Close breaker. |
Reverse
sequence to restore service through line B.
|