Scheme # 32
To
prevent operation (closed, open, or closed) of interrupter
switch when breaker is closed. To prevent opening fuse
compartment door when the interrupter switch A is closed.
To prevent closing interrupter switch until fuse compartment
door is locked closed. Permits the breaker to be serviced
and operated while the interrupter switch is locked open.

Breaker,
fuse compartment door, and interrupter are shown in closed
position, connected to line B. Key A-1 is held in breaker
interlock and key A-2 is held in interrupter interlock.
To service breaker, proceed as follows:
|
|
1.
2.
3.
4.
5.
6.
|
Open breaker.
Turn key A-1 in L-O interlock on breaker to lock open.
Key A-1 is now free.
Insert key A-1 in L-C-O-C interlock on interrupter
and turn to unlock. Key A-1 is now held.
Open interrupter.
Turn key A-1 in L-C-O-C interlock on interrupter to
lock open. Key A-1 is now free.
Return key A-1 to breaker interlock and unlock for
operation of breaker during servicing. |
Reverse
sequence to restore service through either line A
or line B.
To open fuse compartment door:
|
|
1.
2.
3.
4.
|
Proceed from normal position with operations 1 through
4 above.
Turn key A-2 in L-O interlock on interrupter to lock
open. Key A-2 is now free.
Insert key A-2 in L-C interlock on fuse compartment
door and turn to unlock. Key A-2 is now held.
Open fuse compartment door. |
Reverse
sequence to restore service.
To transfer interrupter from line B to line A:
|
|
1.
2.
3.
4.
5.
|
Proceed from normal position with operations as in
steps 1 through 3 above.
Open interrupter switch from line B and connect
to line A.
Turn key A-1 in L-C-O-C interlock on interrupter to
lock closed. Key A-1 is now free.
Insert key A-1 in L-O interlock on breaker and turn
to unlock. Key A-1 is now held.
Close breaker. |
Reverse
sequence to restore service through line B.
|