Interlock Application - Breakers and Generators

Scheme # 35A

To prevent closing the generator breaker when the main breaker is closed.

Interlock Application Scheme # 35 - Breakers and Generators



Breaker A is closed to supply load M. Key A-1 is held in the L-O interlock on breaker A. Generator breaker G is locked open and cannot be closed until breaker A is locked open.

To transfer load M to the generator, proceed as follows:

  1.
2.

3.

4.
Open breaker A.
Turn key A-1 in L-O interlock on breaker A to lock open. Key A-1 is now free.
Insert key A-1 in L-O interlock on breaker G and turn to unlock. Key A-1 is now held.
Close breaker G.


Reverse sequence to restore service through breaker A.

 