- Breakers and Generators
Scheme # 35A
To prevent closing the generator breaker when the main
breaker is closed.

Breaker A is closed to supply load M. Key A-1 is held
in the L-O interlock on breaker A. Generator breaker G
is locked open and cannot be closed until breaker A is
locked open.
To
transfer load M to the generator, proceed as follows:
|
|
1.
2.
3.
4. |
Open breaker A.
Turn key A-1 in L-O interlock on breaker A to lock
open. Key A-1 is now free.
Insert key A-1 in L-O interlock on breaker G and turn
to unlock. Key A-1 is now held.
Close breaker G. |
Reverse sequence to restore service through breaker A.
|