|
Contents
| Introduction
| Symbols
Legend | Scheme
Book
Interlock
Application
- Uninterrupted Power Sources
Scheme # 39
To
prevent improper maintenance bypass of Uninterruptible
Power Supply.

Solenoid Key Release Unit (SKRU) shown with A-1 Key held
captive. UPS output breaker A is closed supplying the
critical load through the UPS. Key B-1 is held captive
in the L-O interlock on breaker A. Maintenance bypass
breaker B cannot be closed until the UPS is placed in
bypass mode, sending a signal to the SKRU allowing release
of key A-1. The SKRU has an apartment lock that will accept
either key A-1 or B-1.
To supply critical load through the maintenance bypass
breaker, proceed as follows:
|
|
1.
2.
3.
4.
5.
6.
7. |
Place the UPS in bypass mode.
Upon receipt of the proper signal, key A-1 in SKRU
can be turned changing status of SKRU internal contacts
and releasing key A-1.
Insert key A-1 in L-O interlock on maintenance bypass
breaker B and turn to unlock.
Close maintenance bypass breaker B. Key A-1 is now
held.
Open UPS output breaker A.
Turn key B-1 in interlock on UPS output breaker A
to lock open. Key B-1 is now free.
Insert key B-1 in SKRU and turn to return the SKRU
internal contacts to the original position. Key B-1
is now held in the SKRU.
|
Reverse
sequence to restore equipment to original condition.
Note:
Refer to UPS manufacturer's operation and maintenance
manual for instructions regarding transferring the load
to the UPS maintenance bypass source. Persons not familiar
with the operation of the UPS system should not attempt
to change the position of the above devices.

|