Scheme # 44
To
prevent opening any rectifier enclosure door while the
rectifier is operating.

Rectifier
with DC output breaker. Any quantity of rectifier access
doors can be accommodated.
Load
break switch A and DC main breaker B are normally closed.
Key A-1 is held in the L-O interlock on breaker B. Key
A-2 is held in the L-O interlock on load break switch
A. All D-1 keys are held in the transfer interlock. All
rectifier enclosure access doors are locked closed.
|
|
1.
2.
3.
4.
5.
6.
7.
8.
|
Open breaker B.
Turn key A-1 to lock the breaker in the open position.
Key A-1 is now free.
Insert key A-1 in L-C interlock on load break switch
A and turn to unlock.
Open load break switch A. Key A-1 is now held.
Turn key A-2 in L-O interlock on load break switch
A and turn to lock the load break switch in the open
position. Key A-2 is now free.
Insert key A-2 in the transfer interlock and turn.
Key A-2 is now held and D-1 keys are free.
Insert D-1 keys in the L-C interlocks (Type D) on
rectifier access doors.
Open the rectifier access doors to enter the rectifier
enclosure. The D-1 keys are held in each door interlock
as long as the door is open. |
Reverse
sequence to restore service.
|