- Rectifier Access
Scheme # 45
To
prevent opening any rectifier enclosure door while the
rectifier is operating and to prevent opening the negative
disconnect switch under load.

Rectifier
with incoming load break switch, DC output breaker and
negative disconnect switch. Any quantity of rectifier
access doors can be accommodated.
Load
break switch A, DC main breaker B and negative disconnect
switch N are normally closed. Key A-1 is held in the L-O
interlock on breaker B. Key A-2 is held in the L-O interlock
on load break switch A. Key N-1 and all D-1 keys are held
in the transfer interlock. All rectifier enclosure access
doors are locked closed.
|
|
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
|
Open breaker B.
Turn key A-1 to lock the breaker in the open position.
Key A-1 is now free.
Insert key A-1 in L-C interlock on load break switch
A and turn to unlock.
Open load break switch A. Key A-1 is now held.
Turn key A-2 in L-O interlock on load break switch
A to lock the load break switch in the open position.
Key A-2 is now free.
Insert key A-2 in the transfer interlock and turn.
Key A-2 is now held. All D-1 keys and key N-1 are
now free.
Insert D-1 keys in the L-C interlocks (Type D) on
rectifier access doors.
Open the rectifier access doors to enter the rectifier
enclosure. The D-1 keys are held in each door interlock
as long as the door is open.
Insert key N-1 in L-C interlock on the negative disconnect
switch N and turn to unlock.
Open negative disconnect switch N. Key N-1 is now
held. |
Reverse
sequence to restore service.
|