Contents
| Introduction
| Symbols
Legend | Scheme
Book
Interlock
Application
- Isolating Switches and Breaker
Scheme # 6
To
prevent operation of disconnect switch A when breakers
B, C, D and E are closed. Breakers may be opened in any
sequence.
NOTE:
Electrical circuit is equivalent of Scheme 7.

Disconnect
A and breakers B, C, D and E are shown in closed position.
Key A-1 is held in transfer interlock. Keys A-2, A-3,
A-4 and A-5 are held in interlocks on breaker B, C, D
and E.
|
|
1.
2.
3.
4.
5.
6.
7.
8.
9.
|
Open breakers B, C, D and E.
Turn key in L-O interlock on each breaker B, C, D
and E to lock breakers open. Keys A-2, A-3, A-4 and
A-5 are now free.
Insert keys A-2, A-3, A-4 and A-5 in transfer interlock.
Turn key A-1 in transfer interlock. Key A-1 is now
free. Keys A-2, A-3, A-4 and A-5 are now held.
Insert key A-1 in L-O-C interlock on disconnect A
and turn to unlock. Key A-1 is now held.
Open disconnect A.
Turn key A-1 in L-O-C interlock on disconnect A to
lock open. Key A-1 is now free.
Insert key A-1 in transfer interlock and turn. Key
A-1 is now held, Keys A-2, A-3, A-4 and A-5 are now
free.
Return keys A-2, A-3, A-4 and A-5, as desired, to
breaker interlocks and unlock for operation during
servicing. |
Reverse
sequence to restore service.
|