Contents
| Introduction
| Symbols
Legend | Scheme
Book
Interlock
Application
- Isolating Switches and Breaker
Scheme # 8
To
prevent operation of disconnects A and B when breaker
C is closed. To permit servicing of breaker when disconnects
are locked open.

Breaker
C and disconnects A and B are shown closed. One key A-1
is held in breaker L-O interlock and the other key A-1
is held in L-O interlock on disconnect B. Key A-2 is held
in L-O interlock on disconnect A.
|
|
1.
2.
3.
4.
5.
6.
7.
8.
9.
|
Open breaker.
Turn key A-1 in L-O interlock on breaker to lock open.
Key A-1 is now free.
Insert key A-1 in L-C interlock on disconnect A and
turn to unlock. Key A-1 is now held.
Open disconnect A.
Turn key A-2 in L-O interlock on disconnect A to lock
open. Key A-2 is now free.
Insert key A-2 in L-C interlock on disconnect B and
turn to unlock. Key A-2 is now held.
Open disconnect B.
Turn key A-1 in L-O interlock on disconnect B to lock
open. Key A-1 is now free.
Insert key A-1 in breaker L-O interlock and turn to
unlock for operation during servicing. |
Reverse
sequence to restore service.
|